After configuration and commissioning, the controller is put into test mode and checked out for proper operation.
CAUTION
Equipment Damage Possible
May cause short-cycling of compressors, or cause damage to other heating or cooling equipment.
You must take appropriate and recommended precautions when initiating the Test Mode. This mode directly drives controller outputs to the manually-entered states.
Place the controller in manual mode. In this mode, the controllers application goes off-line and you can view the outputs within the context of the application schematic.
On-line
Right click on the controller and select the Controller Diagnostics option. Alternatively, select Controller Diagnostics option from the applications main menu.
Select RIO and click OK.
The diagnostic screen for RIO appears.
The diagnostic screen for RIO displays the configured resistive and voltage analog inputs.The configured digital inputs are also displayed.
| Name | Definition |
| Analog Inputs | The configured analog inputs values are displayed according to the project unit.Those values that fall out of range are displayed as Invalid. |
| Digital Inputs | The configured digital inputs are also displayed. |
| Digital Outputs | The outputs along with their values are displayed. |