RIO Diagnostics

Description

After configuration and commissioning, the controller is put into test mode and checked out for proper operation.

Equipment Damage Possible

May cause short-cycling of compressors, or cause damage to other heating or cooling equipment.

You must take appropriate and recommended precautions when initiating the Test Mode. This mode directly drives controller outputs to the manually-entered states.

Purpose

Place the controller in manual mode. In this mode, the controller’s application goes off-line and you can view the outputs within the context of the application schematic.

Mode

On-line

Procedure

Right click on the controller and select the Controller Diagnostics option. Alternatively, select Controller Diagnostics option from the application’s main menu.

Select RIO and click OK.

The diagnostic screen for RIO appears.

The diagnostic screen for RIO displays the configured resistive and voltage analog inputs.The configured digital inputs are also displayed.

Fields

Name Definition
Analog Inputs The configured analog inputs values are displayed according to the project unit.Those values that fall out of range are displayed as “Invalid”.
Digital Inputs The configured digital inputs are also displayed.
Digital Outputs The outputs along with their values are displayed.